Senseware Series
Detectors suitable for detecting flames from light and heavy hydrocarbons
IR3-109/1 flame detector for indoor and outdoor use with triple IR sensor
The IR3-109/1 flame detector is a high-performance device designed for early detection of flames caused by light and heavy hydrocarbons, such as natural gas, oil, wood, or paper. Featuring advanced triple infrared sensor technology, it ensures exceptional immunity to false alarms even in challenging environments, with a 90° field of view for optimal area coverage. Suitable for both indoor and outdoor installations, it boasts an IP65 rating and a rugged, weather-resistant fiberglass (GRP) housing. Certified for use in ATEX Zone 2 and unclassified areas, the IR3-109/1 integrates seamlessly into fire protection systems via 4–20 mA output and dedicated alarm and fault relays. A reliable and versatile solution for fire safety in industrial and commercial environments.
UV-185/5 flame detector for hydrocarbons and hydrogen with ultraviolet sensor
The UV-185/5 flame detector uses an ultraviolet sensor to ensure rapid detection of flames caused by hydrocarbons or hydrogen, delivering high accuracy even in challenging environments. It features a 90° field of view and outstanding immunity to false alarms, making it ideal for high-risk industrial and commercial applications. Designed for both indoor and outdoor installations, it combines a robust construction with electronics engineered to withstand harsh environmental conditions. Certified for use in ATEX Zone 2 and non-classified areas, the UV-185/5 integrates seamlessly into existing fire protection systems via 4–20 mA output and dedicated alarm and fault relays. A dependable solution for facilities requiring UV-based flame detection.
UV/IR-210/1 flame detector for hydrocarbons and hydrogen with dual UV/IR sensors
The UV/IR-210/1 flame detector combines ultraviolet and infrared sensing to ensure rapid detection of flames caused by hydrocarbon or hydrogen combustion. By simultaneously analyzing both optical signals, it delivers fast response and exceptional immunity to false alarms, even in the presence of interference such as solar radiation. Suitable for indoor and outdoor installations, it is certified for use in ATEX Zone 2 and non-classified areas. Its fiberglass (GRP) housing guarantees robustness and long-term durability, even under harsh environmental conditions. Integration into fire protection systems is straightforward via 4–20 mA output and dedicated alarm and fault relays. The UV/IR-210/1 is a reliable and effective solution for fire safety in high-risk industrial environments.
Integration and additional options
SM21 – Adjustable swivel bracket
Adjustable swivel bracket for positioning the detector’s field of view
TC-169/1 – Test Lamp
Non-EX certified test lamp for checking the correct operation of flame detectors in fire-risk areas
arrow_back
arrow_forward
This product is available in the following versions

IR3-109/1
IR3 Flame detector

UV-185/5
UV Flame detector

UV/IR-210/1
UV/IR Flame detector
Technical Specifications
| IR3-109/1 | UV-185/5 | UV/IR-210/1 | |
| Power supply voltage | 10–28 Vdc | 10–28 Vdc | 10–28 Vdc |
| Current draw | 25 to 40 mA | 25 to 40 mA | 25 to 40 mA |
| IP Class | IP 65 | IP 65 | IP 65 |
| Range of view | 0.09 m² of n-heptane at 35 m | 0.09 m² of n-heptane at 23 m | 0.09 m² of n-heptane at 23 m |
| Sensitivity | Class 1 (EN 54-10) | Class 2 (EN 54-10) | Class 2 (EN 54-10) |
| Coverage angle | 90° cone | 90° cone | 90° cone |
| Frequency response | 2.7 to 5 μm | 185–260 μm | 185–260 nm / IR: 2.7 μm |
| Operating temperature | -25° ... +70°C | -25° ... +70°C | -25° ... +70°C |